COP edit

COP claims for heat pumps are controversial and consequently need good references. I don't see a reference for the claim "The EcoCute derives two units of energy from ambient air temperature for every unit of electrical power it requires. Each of these one unit plus two cost free units ..."

The comparison of the COP against a gas boiler is also misleading for two reasons. Firstly, modern gas boilers don't have a pilot light loss for the simple reason that they no longer have a pilot light! Secondly, and more important, when comparing electrically powered devices against direct use of primary fuels it is necessary to consider the carbon emissions of the electricity generating stations. This varies hugely from country to country. 131.111.85.79 (talk) 15:44, 7 January 2009 (UTC)Reply

COP again edit

"The EcoCute's COP is 3.8 in industrial use, while electric power water heating is 1.0, and gas boiler is 0.88 including pilot light loss." Comparing COP and efficiencies (in this case for water heater and boiler) is misleading at best, false in most cases. For such comparisons (especially next to carbon footprint claims), it is probably better to compare primary energy usage. Laurentsavaete (talk) 18:38, 17 January 2009 (UTC)Reply


COP of gas boilers varies widely from around 65% to almost 100%, depending on design. Its simply incorrect to attribute it any one fixed figure.

Also a heat pumps claimed figure doesn' equal real life performance, since the real world COP varies very widely depending on input and output temps. So to compare a manufacturer's spec, which will always be for optimistic conditions, as if it were a fixed figure, with other heating options is really very misleading. 82.31.207.100 (talk) 22:03, 3 July 2009 (UTC)Reply

External links modified edit

Hello fellow Wikipedians,

I have just modified one external link on EcoCute. Please take a moment to review my edit. If you have any questions, or need the bot to ignore the links, or the page altogether, please visit this simple FaQ for additional information. I made the following changes:

When you have finished reviewing my changes, you may follow the instructions on the template below to fix any issues with the URLs.

This message was posted before February 2018. After February 2018, "External links modified" talk page sections are no longer generated or monitored by InternetArchiveBot. No special action is required regarding these talk page notices, other than regular verification using the archive tool instructions below. Editors have permission to delete these "External links modified" talk page sections if they want to de-clutter talk pages, but see the RfC before doing mass systematic removals. This message is updated dynamically through the template {{source check}} (last update: 18 January 2022).

  • If you have discovered URLs which were erroneously considered dead by the bot, you can report them with this tool.
  • If you found an error with any archives or the URLs themselves, you can fix them with this tool.

Cheers.—InternetArchiveBot (Report bug) 17:46, 16 September 2017 (UTC)Reply

Ref.: "EcoCute machine basics": Doubts edit

Section "EcoCute machine basics" subsection (3) must contain an error:

 "...to produce hot water. Water temperatures around 5°C and up are suitable at this stage."

I don't know the exact value, but 95°C or higher seems more appropriate to the hot side.

As of my knowledge, CO2 heat pumps may transfer energy from -20°C ... +30°C up to 60°C ... 90°C (special pumps may reach more than 100°C).

--Ewlcsg (talk) 15:07, 21 August 2018 (UTC)Reply

5 °C is being since initial edit 2008, Doubts in 2018. Missed pay atten. Talk page, might typo. For 5 0°C, Sorry for delaying 5 year.@ Namazu-tron (talk) 10:58, 6 February 2024 (UTC)Reply