In building safety and construction, a smokeproof enclosure is a type of exit stairwell that has been designed to keep out smoke (and other combustion products) in the event of a fire, so that building occupants may more safely exit the building.[1][2][3][4][5]

Description

edit

Rather than entering the stairwell directly from the building interior, one enters a smokeproof enclosure by means of an open-air balcony or alternatively, a so-called open vestibule, and proceeds thence, to the stairwell itself.[1] The way that the balcony or vestibule is ventilated divides smokeproof enclosures into two basic types: mechanically ventilated which is not actually a smokeproof enclosures, where the vestibule and stairwell are ventilated by mechanical equipment, and naturally ventilated open air smokeproof enclosures where the open balcony or vestibule [or the stairwell] has openings directly to the outside of the building. This is the only type of the original concept of a smokeproof tower (i.e.: smokeproof enclosure).[6][3]

US requirements

edit

Under United States building codes, the stairwell of a smokeproof enclosure must have walls with a 2-hour fire resistance rating and vestibule doors (if provided) with a 1.5 hour fire resistance rating.[7] The Life Safety Code states that such stairwells be "approved systems with a design pressure difference across the barrier of not less than 0.05 in. water column (12.5 Pa) in sprinkled buildings and 0.10 in. water column (25 Pa) in non-sprinkled buildings".[4] Approved, in the Life Safety Code, means the committee didn't want to 'decide' so, left it up to someone else to decide a particular issue.

In the so-called mechanically ventilated smokeproof enclosures, the stairwell is positively pressurized relative to the rest of the building.[6][8] This ensures that even when access doors are opened, smoke will not enter the stairwell.[8][4] Of course, a higher pressure within a stairwell makes it harder to open doors from the building interior to the enclosed vestibules and to the enclosed stairwell.[9] The Life Safety Code requires that the pressure differential across the barrier not be so great as to prevent the door from opening with a force of 30 lbf (133 N) at the door knob or handle.[4] These 'pressurization' problems are, of course, non-existent with naturally ventilated smokeproof enclosures.

The fans and air ducts used to pressurize the stairwell are life-critical systems, and are required to be enclosed in non-combustible, likewise two hour rated, construction.[4] (For fully sprinkled buildings, the required rating is just one hour.)[4] The fans must be connected to an emergency power supply, and capable of both automatic activation by various fire and smoke detectors, and of manual activation by a central command post or by the actuation of a general fire alarm.[4]

References

edit
  1. ^ a b Bush 1988, p. 328.
  2. ^ Lathrop 1993, p. 83.
  3. ^ a b Scott 1997, pp. 201–202.
  4. ^ a b c d e f g Burke 2008, pp. 265–266.
  5. ^ Chowdhury 1999.
  6. ^ a b Clet 1978, p. 113.
  7. ^ Allen 2004, §5.2.3.
  8. ^ a b Binggeli 2011, p. 68.
  9. ^ FIPP 2012, pp. 235.

Sources

edit
  • Allen, James Elmore (2004). Assisted living administration: the knowledge base (2nd ed.). Springer Publishing Company. ISBN 978-0-8261-1516-4.
  • Binggeli, Corky (2011). "Structural Systems § Exit Stairs". Building Systems for Interior Designers (2nd ed.). John Wiley and Sons. ISBN 978-1-118-17432-6.
  • Burke, Robert A. (2008). Fire protection: systems and response. CRC Press. ISBN 978-1-56670-622-3.
  • Bush, Vincent R. (1988). Handbook to the uniform building code: an illustrative commentary. International Conference of Building Officials.
  • Clet, Vince H. (1978). Fire-related codes, laws, and ordinances. Glencoe Press fire science series. Glencoe Publishing Co. ISBN 978-0-02-471760-3.
  • Fire Inspector: Principles and Practice. Jones & Bartlett Publishers. 2012. ISBN 978-1-4496-5527-3.
  • Lathrop, James K., ed. (1993). Life safety code handbook (5th ed.). National Fire Protection Association. ISBN 978-0-87765-379-0.
  • Scott, James G. (1997). Architectural building codes: a graphic reference. John Wiley & Sons. ISBN 978-0-471-28655-4.

Further reading

edit
  • Ferreira, Michael J.; Klote, John H. (February 2, 2011). "Rethinking the 'smokeproof' enclosure". Consulting Specifying Engineer.
  • Patterson, James (1993). "Exits and Egress". Simplified design for building fire safety. Parker-Ambrose series of simplified design guides. Vol. 16. §7.5.4: Wiley-IEEE. pp. 172–178. ISBN 978-0-471-57236-7.{{cite book}}: CS1 maint: location (link)
  • Dillon, Michael Earl (2002). "Smoke Control Systems". In Solomon, Robert E. (ed.). Fire and Life Safety Inspection Manual. NFPA (8th ed.). § Smokeproof Enclosures: Jones & Bartlett Learning. pp. 115–116. ISBN 978-0-87765-472-8.